copyright 2002-2003 by:
 
web factory
last update 25/11/2003 |
|
credits
|
| |
|
THREE
PHASE POWER TRANSFORMERS TTP RANGE |
| POWER |
INPUT |
OUTPUT |
FREQUENCY |
STANDARDS |
| FROM
1KVA TO 100KVA |
DA 220V A 500V
|
DA 220V A 500V
|
50/60
Hz |
EN
61558-2-1 |
| CEI
14-4 |
| BS
141 |
| |
Open type
Protection IP00
Isolation class F (Ta max 45°C)
Separatecopper windings cl. H
Resin impregnated and tropicalised
Coonections on terminal blocks to 20kVA (or 63A)
Connections on brass bolts from 25kVA (or from 64A)
Grain oriented magnetic core form 25kVA
Vector group: Dyn11
(standard)
Encapsulated in metal enclosure on request |


|

|
| power |
part
no. |
losses
(W) |
short
circ. |
regulation |
dimensions
mm. |
DIS |
weight |
box |
| KVA |
no
load |
on
load |
voltage
% |
% |
A |
B |
C |
D |
E |
F |
kg. |
code |
| 1 |
TTP2202 |
15 |
55 |
4.5 |
3.5 |
240 |
150 |
185 |
175 |
85 |
6 |
A |
15.5 |
MBT02 |
| 2 |
TTP2204 |
28 |
90 |
4.5 |
3.5 |
240 |
175 |
185 |
175 |
110 |
6 |
A |
23.0 |
MBT02 |
| 3 |
TTP2206 |
42 |
120 |
4.5 |
3.0 |
300 |
180 |
230 |
220 |
100 |
6 |
A |
29.5 |
SA01 |
| 4 |
TTP2208 |
60 |
160 |
4.5 |
3.0 |
300 |
190 |
230 |
220 |
110 |
6 |
A |
34.0 |
SA01 |
| 5 |
TTP2209 |
70 |
200 |
4.0 |
3.0 |
360 |
210 |
275 |
280 |
130 |
8 |
A |
44.0 |
SA02 |
| 6 |
TTP2210 |
70 |
220 |
4.0 |
3.0 |
360 |
210 |
275 |
280 |
130 |
8 |
A |
47.5 |
SA02 |
| 8 |
TTP2211 |
90 |
260 |
4.0 |
3.0 |
360 |
230 |
275 |
280 |
150 |
8 |
A |
63.0 |
SA02 |
| 10 |
TTP2212 |
90 |
280 |
4.0 |
3.0 |
360 |
230 |
275 |
280 |
150 |
8 |
A |
66.5 |
SA02 |
| 12.5 |
TTP2213 |
100 |
280 |
4.0 |
3.0 |
420 |
240 |
320 |
300 |
130 |
8 |
A |
83.0 |
SA03 |
| 15 |
TTP2214 |
120 |
350 |
4.0 |
3.0 |
420 |
250 |
320 |
300 |
140 |
8 |
A |
101.0 |
SA03 |
| 20 |
TTP2215 |
150 |
420 |
3.5 |
3.0 |
420 |
260 |
320 |
300 |
150 |
8 |
A |
113.0 |
SA03 |
| 25 |
TTP2216 |
160 |
460 |
3.5 |
3.0 |
480 |
290 |
465 |
370 |
190 |
10 |
B |
115.0 |
SA04 |
| 30 |
TTP2217 |
250 |
700 |
3.5 |
3.0 |
540 |
270 |
510 |
490 |
200 |
10 |
B |
145.0 |
SA05 |
| 40 |
TTP2218 |
250 |
750 |
3.5 |
3.0 |
540 |
270 |
510 |
490 |
200 |
10 |
B |
168.0 |
SA05 |
| 50 |
TTP2219 |
250 |
800 |
3.5 |
3.0 |
540 |
270 |
510 |
490 |
200 |
10 |
B |
180.0 |
SA05 |
| 60 |
TTP2220 |
320 |
900 |
3.5 |
3.0 |
690 |
340 |
660 |
600 |
210 |
10 |
B |
250.0 |
SA07 |
| 70 |
TTP2221 |
350 |
1000 |
3.5 |
3.5 |
690 |
340 |
660 |
600 |
210 |
10 |
B |
280.0 |
SA07 |
| 80 |
TTP2222 |
350 |
1100 |
3.5 |
3.5 |
690 |
340 |
660 |
600 |
210 |
10 |
B |
310.0 |
SA07 |
| 90 |
TTP2223 |
370 |
1250 |
3.5 |
3.5 |
690 |
340 |
660 |
600 |
210 |
10 |
B |
330.0 |
SA07 |
| 100 |
TTP2224 |
400 |
1300 |
3.5 |
3.5 |
690 |
340 |
660 |
300 |
210 |
10 |
B |
350.0 |
SA07 |
| ASK
FOR CODES AND SPECIFICATION OF HIGHER RATINGS |
|
|
THE PART
NO. REPRESENTS THE STANDARD PRODUCT WITH INOUT/OUTPUT VOLTAGE
230V. FOR DIFFERENT VOLTAGES, THE ORDER SHALL INCLUDE THE
REQUIRED INPUT/OUTPUT VOLTAGE |
|
|
WHEN A
DIFFERENT VECTOR GROUP IS REQUIRED, THIS SHALL BE INDICATED IN
THE ORDER |
|
|
DIMENSIONAL
DATA ARE REFERRED TO THE STANDARD IN 400V / OUT 230V TYPE.
DIMENSIONS AND WEIGHTS MAY VARY ACCORDING TO THE SPECIFIC
INPUT/OUTPUT VOLTAGE REQUIRED |
|
|
UL RECOGNIZED COMPONENT (USA)
VERSION AVAILABLE

CONTACT US FOR YOUR ENQUIRIES |
|
|
A |

|
|
B |

|
|
|
Data shown
on this page are for reference only and can be changed withouth further notice
|
|